- Increasing Power Plant Efficiency with 15 % and decreasing the consumption of the natural gas with 25% in Summer Season by Modification of Cooling tower System
-
Increasing Power Plant Efficiency with 15 % and decreasing the consumption of the natural gas with 25% in Summer Season by Modification of Cooling tower System
BY ENG. OSAMA SALAMA ELSAYED
EGYPTIAN PETROCHEMICALS CO .
(LOAN TO EGYPTIAN ETHYLENE AND DERIVATIVES COMPANY)
EMAIL: – osalama@ethydco-eg.com
Tel :- 01113588933
PROJECT GENERAL MANAGER
- Sc IN MECH. ENGINEERING
Abstract
Power station plant (combined cycle) consist of Gas turbine GT9 (32 MW h), Gas Turbine GT8C (52MW h) and Steam Turbine (36 MW h) which supply the Companies ( Sidpec , Gasco, Alex. Fiber& EPC) by electrical power and process steam
The Cooling System Contains No.7 Cells Cooling Tower To Feed Cold Water To Process Plant ( PVC , VCM , CL2 And Utility Plants) which required minimum cooling water inlet temperature (Max. 27 ºC) And the heat duty equal 56 M Kcal / h And The steam turbine condenser of the power plant require inlet water temperature ( Max. 35 ºC) and heat duty equal 78 M Kcal / h so the steam turbine output power 36 MW h .
There Are a Problem In Cooling Water System specially in summer season when the steam turbine operation with the process plants, Because The Return Cooling Water Temperature increased due to increasing air wet bulb temperature and due to heat load of steam turbine condenser, So to keep the process plants in operation 100 % load capacity, then we must stop the steam turbine consequently the power losses shall be 36 MW h (7 months) stop every year
EPC solved this problem By separation No. 2 Cells film type filling from the total No. 7 Cells to be in continuous operation with the power station plant, So the steam turbine power generation reached to 31.3 MW h . And The No.5 cells to be in operation with the process plants. Then the cooling water outlet temperature of the No. 5 Cells shall reach to the minimum value due to cooling tower max. Approach 2 ºC and the VCM plant shall be loaded with 100% Capacity.
- Increasing Power Plant Efficiency with 15